Determining operation schedules of heat recovery ventilators for optimum energy savings in high-rise residential buildings

Cited 18 time in webofscience Cited 0 time in scopus
  • Hit : 497
  • Download : 0
DC FieldValueLanguage
dc.contributor.authorKim, Sang-Minko
dc.contributor.authorLee, Ji-Hyunko
dc.contributor.authorKim, Sooyoungko
dc.contributor.authorMoon, Hyeun Junko
dc.contributor.authorCho, Jinsooko
dc.date.accessioned2013-03-11T03:04:28Z-
dc.date.available2013-03-11T03:04:28Z-
dc.date.created2012-04-19-
dc.date.created2012-04-19-
dc.date.issued2012-03-
dc.identifier.citationENERGY AND BUILDINGS, v.46 Special, no.SI, pp.3 - 13-
dc.identifier.issn0378-7788-
dc.identifier.urihttp://hdl.handle.net/10203/98092-
dc.description.abstractThis study examines the influence of heat recovery ventilators (HRVs) on energy savings in high-rise residential buildings to determine optimum operation schedules. Field measurements were conducted in two actual residential buildings, and computer simulations were performed to predict energy savings by the HRVs. Measurement results showed that energy consumption in each building was reduced when the HRVs were operated in line with recommended ventilation rates and comfortable temperature ranges. The HRVs achieved greater savings of energy during winter than summer. Simulation results showed that the HRVs contributed to the annual savings of heating and cooling energy by 9.45% and 8.8%, respectively, when the ventilators were operated continuously for 24 h. More energy was saved as the operating hours of the HRVs increased. The continuous operation of HRVs was effective for the savings of energy and to maintain recommended ventilation rates. The HRVs achieved effective energy savings and maintained necessary ventilation rates in high-rise residential buildings where natural infiltration was minimal, due to tightly sealed building envelopes. This study suggests that the influence of HRVs on the improvement of indoor air quality needs to be examined in conjunction with energy savings by HRVs. (c) 2011 Elsevier B.V. All rights reserved.-
dc.languageEnglish-
dc.publisherELSEVIER SCIENCE SA-
dc.subjectPERFORMANCE-
dc.subjectAIR-
dc.subjectSYSTEMS-
dc.titleDetermining operation schedules of heat recovery ventilators for optimum energy savings in high-rise residential buildings-
dc.typeArticle-
dc.identifier.wosid000301750600002-
dc.identifier.scopusid2-s2.0-84857044060-
dc.type.rimsART-
dc.citation.volume46 Special-
dc.citation.issueSI-
dc.citation.beginningpage3-
dc.citation.endingpage13-
dc.citation.publicationnameENERGY AND BUILDINGS-
dc.identifier.doi10.1016/j.enbuild.2011.10.053-
dc.contributor.localauthorLee, Ji-Hyun-
dc.contributor.nonIdAuthorKim, Sang-Min-
dc.contributor.nonIdAuthorKim, Sooyoung-
dc.contributor.nonIdAuthorMoon, Hyeun Jun-
dc.contributor.nonIdAuthorCho, Jinsoo-
dc.type.journalArticleArticle-
dc.subject.keywordAuthorHeat recovery ventilator-
dc.subject.keywordAuthorOptimum operation schedule-
dc.subject.keywordAuthorEnergy savings-
dc.subject.keywordAuthorNatural infiltration-
dc.subject.keywordAuthorHeat exchange-
dc.subject.keywordAuthorResidential building-
dc.subject.keywordPlusPERFORMANCE-
dc.subject.keywordPlusAIR-
dc.subject.keywordPlusSYSTEMS-
Appears in Collection
GCT-Journal Papers(저널논문)
Files in This Item
There are no files associated with this item.
This item is cited by other documents in WoS
⊙ Detail Information in WoSⓡ Click to see webofscience_button
⊙ Cited 18 items in WoS Click to see citing articles in records_button

qr_code

  • mendeley

    citeulike


rss_1.0 rss_2.0 atom_1.0