dc.description | 학위논문(석사) - 한국과학기술원 : 핵공학과, 1986.2, [ ix, 101 p. ] | - |
dc.description.abstract | A new approach is proposed here for the level control of steam generators through a weighted one-step- ahead stochastic self-tuning algorithm. The complicated steam generator model is represented by four parameters; water level, feedwater, steam flow and stochastic disturbances. A set of time series difference equations are obtained by combining these parameters and the measurements of water level, feedwater flow, and steam flow. These parameters are determined by a recursive least squares algorithm which results from minimizing the sum of the squared error between output (steam generator water level) and one-step-ahead optimal prediction of output. This algorithm contains a forgetting factor which can be used to account for an exponential decay of past data in tracking a slow drift in the parameters. The recursive least squares with forgetting factor, $0.950 < \lambda < 0.995$, shows good performance when rapid changes occur in process. Control input is calculated by using the time series difference equation so that the one-step-ahead optimal prediction of output equals to desired output. However, excessive control effort may be called for to bring output to desired output. Therefore, the present weighted one-step-ahead controller is designed to achieve a compromise between the extent of bringing output to desired output and the amount of control effort. An additional integral action controller is adopted optionally to compensate for the steady-state offset which comes from non-zero mean disturbances or control input weighting. To measure water level, feedwater flow, and steam flow accurately, the conventional D/P cells are replaced by capacitance-type transducers. The transducers give excellent linearity, even in the very low $\triangle$P range. The experimental loop, which is a mock-up of the secondary loop of the nuclear power plant, is used to prove effectiveness of the present adaptive control algorithm. It can be concluded from experimental results that ... | eng |
dc.language | eng | - |
dc.publisher | 한국과학기술원 | - |
dc.subject | 핵증기 발생기. | - |
dc.title | Experimental studies of adaptive control system for nuclear steam generators | - |
dc.title.alternative | 증기 발생기의 적응 제어시스템에 대한 실험적 연구 | - |
dc.type | Thesis(Master) | - |
dc.identifier.CNRN | 65467/325007 | - |
dc.description.department | 한국과학기술원 : 핵공학과, | - |
dc.identifier.uid | 000841314 | - |
dc.contributor.localauthor | Cho, Byung-Hak | - |
dc.contributor.localauthor | 조병학 | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.