Estimation of the flow profile correction factor of a transit-time ultrasonic flow meter for the feedwater flow measurement in a nuclear power plant

Cited 13 time in webofscience Cited 0 time in scopus
  • Hit : 1082
  • Download : 1147
A new method to estimate the flow profile correction factor (FPCF) for a transit-time ultrasonic flow meter (UFM) having a diametral transducer configuration is introduced in this work. For the adaptation of a diametral UFM for a feedwater measurement, the optimized flow profile correction factor is obtained through experiments and a simulation in actual flow conditions. The log function curve fitting is performed on a combined data set; the velocity ratio of UFM reading versus standard fluid measurement at low flow velocity, UFM reading versus standard fluid measurement at medium flow velocity, and UFM reading versus clean Venturi measurement at high flow velocity. Through an uncertainty analysis, the uncertainty of the FPCF is calculated. The resultant uncertainty of the new FPCF is 0.335%. This value is approximately half the value presented by UFM manufacturers. By adaptation of a diametral UFM with the new FPCF proposed in this work, feedwater flow measurement in nuclear power plants (NPPs) can be easily performed at lower cost than either chordal or cross-correlation UFM.
Publisher
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Issue Date
2005-06
Language
English
Article Type
Article
Citation

IEEE TRANSACTIONS ON NUCLEAR SCIENCE, v.52, no.3, pp.714 - 718

ISSN
0018-9499
URI
http://hdl.handle.net/10203/1720
Appears in Collection
NE-Journal Papers(저널논문)
Files in This Item
This item is cited by other documents in WoS
⊙ Detail Information in WoSⓡ Click to see webofscience_button
⊙ Cited 13 items in WoS Click to see citing articles in records_button

qr_code

  • mendeley

    citeulike


rss_1.0 rss_2.0 atom_1.0